All Categories

Braking Unit

Home >  Products  >  Braking Unit

Inverter special energy consumption JH-DR-4SA brake unit

Inverter special energy consumption JH-DR-4SA brake unit

  • Overview
  • Parameter
  • Inquiry
  • Related Products

Parameter list

Product
model

Recommended resistance

Rated current

Maximum current

Operating voltage

Setting method

Parallel function

AC220V

Modified by the jumperpin holder S1 of themain control board

without

JH-DR-1LK

33Ω

6A

33A

340,360

380,400

Default:360V

JH-DR-1SK

20Ω

10A

75A

with

JH-DR-3SK

9.1Ω

15A

100A

AC380V

JH-DR-1L

33Ω

6A

33A

620,640,

680,720;

Default:640V

Modified by the jumper pin holder S1 of the main control board

without

JH-DR-1G

20Ω

9A

75A

JH-DR-2G

13.6Ω

12A

100A

JH-DR-1SA

20Ω

10A

75A

620,640,

680,720;

Default:680V

with

JH-DR-3SA

13.6Ω

15A

100A

JH-DR-4SA

9.1Ω

25A

150A

JH-DR-2HN

7.5Ω

30A

150A

580,610,640

670,700,730The setting range is shown in table2-3

Default:670V

with

JH-DR-3HN

5.6Ω

70A

150A

JH-DR-4HN

4.0Ω

85A

200A

JH-DR-5HN

2.

120A

300A

JH-DR-6HN

2.

160A

450A

JH-DR-3HA

5.6Ω

70A

150A

The setting range is shown in table2-4;

Default:675V

Set this parameter by the operation panel. For details, see Table 4-5

JH-DR-4HA

4.0Ω

85A

200A

JH-DR-5HA

2.

120A

300A

JH-DR-6HA

2.

160A

450A

AC660V

JH-DR-3HN-6

10Ω

70A

150A

1010,1050

1090,1130

1170,1190

The setting range is shown in table2-3

Default:1130

Modified by the jumper pin holder S1 of the main control board

with

JH-DR-4HN-6

7.5Ω

85A

200A

JH-DR-5HN-6

5.0Ω

120A

300A

JH-DR-6HN-6

3.5Ω

160A

400A

Table 2-1 Models and specifications of brake units

Rated current:refers to the maximum average current when the brake unit is working.

Peak current:refers to the maximum current allowed through the brake unit when it is working, and the longest duration of the current should not exceed 20 seconds.

Universal operating voltage jumper (main control board jumper pin holder S1) selection table

220V

380V

A

340V

A

620V

B

360V

B

640V

C

380V

C

680V

D

400V

D

720V

Table 2-2 Economic and general operating voltage selection table

HA HN-6 operating voltage jumper (main control board jumper pin holder S1) selection table

220V

380V

660V

A

320V

A

580V

A

1010V

B

340V

B

610V

B

1050V

C

360V

C

640V

C

1090V

D

380V

D

670V

D

1130V

E

400V

E

700V

E

1170V

F

420V

F

730V

F

1190V

Table 2-3 Selection of HN operating voltage jumpers

HA type product action voltage selection table

Gear position

1

2

3

4

5

6

7

8

9

10

380V

610

615

625

635

645

655

665

675

685

695

460V

710

715

725

735

745

755

765

775

785

795

Table 2-4 Operation voltage selection table for HA products

GET IN TOUCH