Resistive Load Bank Built to Handle High Power Loads Safely While Offering Accurate Measurement and Monitoring Functions
One-line Pitch A 100 kW, DC 120 V adjustable load bank in a 150 kg wheeled cabinet: twelve resistive and capacitive steps with 100 W resolution, set locally on a touch screen or remotely over CAN, for load, burn-in and battery-discharge testing up to 7×24. Product Features 1.1 100 kW in One Cabinet ...
A 100 kW, DC 120 V adjustable load bank in a 150 kg wheeled cabinet: twelve resistive and capacitive steps with 100 W resolution, set locally on a touch screen or remotely over CAN, for load, burn-in and battery-discharge testing up to 7×24.
Twelve combinable steps — 100 W, 200 W, 200 W, 500 W, 1 kW, 2 kW, 2 kW, 4 kW, 10 kW, 20 kW, 20 kW and 40 kW — add up to exactly 100 kW, so the full rating is reachable in 100 W increments rather than a handful of coarse blocks. A 55 kW test point, for example, is 40 kW + 10 kW + 4 kW + 1 kW.
Both resistive (R) and capacitive (C) step banks are built into the same chassis, with power factor 0.99. One cabinet can therefore present a clean resistive load, or a resistive-plus-capacitive mix, instead of buying and wiring two separate banks and re-cabling between tests.
Set steps on the touch screen at the cabinet, or drive the same steps over CAN from a PLC, host computer or test bench, so one operator can run a load profile unattended. Voltage, current and power read out live at measurement accuracy class 0.5S, which is precise enough to record test data rather than just watch it.
Forced front-to-rear air cooling, resistors rated for a 15-year service life, and rated for continuous online operation around the clock. Over-voltage protection, over-temperature alarm, fan-fault alarm and an emergency stop cover the failure modes that matter during unattended runs; the enclosure is IP20 for indoor use.
Rated DC 120 V, 100 kW, power factor 0.99, which works out to roughly 833 A of load current at rated voltage (calculated from rated power ÷ rated voltage). Maximum permissible voltage is 1.1 × rated, i.e. about 132 V; the load must not be operated beyond that. Auxiliary supply is AC 220 V.
By combining steps. The twelve steps sum to 100 kW and the smallest is 100 W, so any target can be assembled from them: 55 kW = 40 + 10 + 4 + 1 kW; 1.3 kW = 1 kW + 200 W + 100 W. R and C banks are configured separately, so resistive and capacitive load can be set to different values in the same run.
Yes on both counts. Local control is a touch screen; remote control is CAN, so a PLC or host computer can select steps, run a profile and repeat it for every unit. Measurement is class 0.5S for voltage, current and power. For unattended runs the unit carries over-voltage protection, over-temperature alarm, fan-fault alarm and an emergency stop, and is rated for 7×24 continuous operation.
Cooling is forced air, front intake to rear exhaust, so the front and rear faces must stay unobstructed; install indoors (IP20) in a dry, well-ventilated place between −10 and 50 °C. Load is connected by copper busbar, auxiliary power by terminal block. The cabinet measures ≤ 800 × 700 × 1300 mm (L × W × H), weighs ≤ 150 kg and moves on casters.
| Model name | JH-RYF-100KWD120-P |
| Brand | JIANHONG |
| Specification | ≤ 800 × 700 × 1300 mm (L × W × H) |
| Weight | ≤ 150 kg |
| Rated voltage | DC 120 V |
| Rated power | 100 kW |
| Auxiliary power supply | AC 220 V |
| Power factor | 0.99 |
| Resistance accuracy | ±3% (high-precision, compact, ultra-light resistors) |
| Cooling system | Forced air cooling, front intake, rear exhaust |
| Working environment | Operating temperature: −10 to 50 °C; dry, well-ventilated |
| Local mode | Touch screen |
| Remote Control | CAN communication |
| IP class | IP20 (indoor environment) |
| Display mode | Voltage, current and power displayed (measurement accuracy class 0.5S) |
| Adjustable Steps | 100 W, 200 W, 200 W, 500 W, 1 kW, 2 kW, 2 kW, 4 kW, 10 kW, 20 kW, 20 kW, 40 kW (combinable) |
| Load protection | Over-temperature protection, over-voltage protection |
| Step Resolution | 100 W |
| Load Note | Maximum voltage: 1.1 × rated voltage |
| Load Protection | Over-voltage protection, over-temperature alarm, emergency stop, fan fault alarm |
| Duty Cycle | Continuous online operation, 7×24 duty; resistor service life 15 years |
| Load Connection | Copper busbar |
| Auxiliary Power Connection | Terminal block |
| Enclosure Colour | Computer white DH-1928 |
| Mobility | Casters |