Resistive Load Bank Engineered for Electrical Load Testing with Features Ensuring Safety Stability and Accurate Load Control
One-line Pitch Six independent 4 kW resistor channels at DC 800 V in one 40 kg cabinet: 24 kW of loading, 1 kW per step, six sets of threaded terminals so six DC sources can be loaded at the same time — and casters plus a carry handle so it moves between bench, aging room and site. Product Features ...
Six independent 4 kW resistor channels at DC 800 V in one 40 kg cabinet: 24 kW of loading, 1 kW per step, six sets of threaded terminals so six DC sources can be loaded at the same time — and casters plus a carry handle so it moves between bench, aging room and site.
Rated power is 4 kW × 6 channels: six separate resistor branches, each brought out to its own threaded terminal pair, so six DC outputs can be loaded at the same time instead of being tested one after another. Total capacity is 24 kW (4 kW × 6, calculated), and each channel switches independently, which is what makes side-by-side comparison of six units possible on a single bench.
Each channel is built from 1 kW, 1 kW and 2 kW steps that can be stacked, giving 1 kW resolution over a 4 kW range — 1 kW, 2 kW, 3 kW or 4 kW on any channel. The step value is specified at the 800 V rated voltage; at a lower bus voltage the same resistor delivers less power, following Ohm's law (see Q2), so the effective step shrinks proportionally.
610 × 400 × 780 mm and ≤ 40 kg, with a carry handle on top and casters underneath — light enough for two people to lift onto a bench, small enough to park beside a rack. Load enters through six sets of threaded terminals, auxiliary power through a standard socket, and the enclosure is stainless-finish sheet metal with side ventilation grilles.
Each step is switched by an air circuit breaker, so there is no controller or firmware between the operator and the load. Protection covers over-temperature, over-voltage, over-current and an emergency stop; cooling is a 15050 fan moving air right to left; resistance tolerance is ±3% on sheet resistors. Rated for continuous online operation on a 7×24 duty cycle, indoor IP20, with a 1-year warranty.
Yes. Six separate resistor branches are brought out to six sets of threaded terminals, each rated 4 kW at DC 800 V, for 24 kW in total (4 kW × 6, calculated). Each branch is switched by its own air circuit breaker, so any channel can be loaded, left idle or stepped up without affecting the others.
The resistor is fixed, so power follows P = U²/R. A 4 kW / 800 V channel is about 160 Ω, which gives 4 kW at 800 V, 1 kW at 400 V and 0.25 kW at 200 V (all calculated) — the 1 kW step scales the same way. Rated power is therefore reached only at 800 V, and the maximum admissible voltage is 1.1 × rated, i.e. 880 V, where a channel would draw about 4.8 kW.
By air circuit breakers, one per step. Each channel offers 1 kW, 1 kW and 2 kW steps that can be combined, so the smallest increment is 1 kW at 800 V and the maximum is 4 kW per channel. No software or external controller is involved: set the breakers, read the result on your own instrument at the source under test.
Cooling is forced air from right to left through one 15050 fan, so the right-hand intake and the left-hand exhaust must stay clear; install indoors, dry and well-ventilated, at −10 to 50 °C, IP20. Protection covers over-temperature, over-voltage, over-current and emergency stop. The unit is rated for continuous 7×24 operation with a 1-year warranty.
| Model name | JH-RYF-4KWD800-W3K-6L-EMC |
| Brand | JIANHONG |
| Specification | ≤ 610 × 400 × 780 mm (L × W × H) |
| Weight | ≤ 40 kg |
| Rated voltage | DC 800 V |
| Rated power | 4 kW × 6 channels |
| Auxiliary power supply | AC 220 V 50 Hz |
| Power factor | 1 |
| Resistance accuracy | ±3% (sheet resistor) |
| Cooling system | Forced air cooling, right-to-left airflow, 15050 fan |
| Working environment | Operating temperature: -10 to 50 °C; dry and well-ventilated |
| Control Method | Air circuit breaker (MCB) control |
| IP class | IP20 (indoor environment) |
| Power Steps | 1 kW, 1 kW, 2 kW (can be combined) |
| Load protection | Over-temperature, over-voltage, over-current, emergency stop |
| Step Resolution | 1 kW |
| Load Note | 1. Rated power is reached only at the rated voltage of 800 V; at any other voltage the power follows Ohm's law. 2. Maximum voltage is 1.1 × rated voltage. |
| Duty Cycle | Continuous online operation, 7×24 duty; 1-year warranty |
| Load Input | 6 sets of threaded terminals |
| Auxiliary Power Input | Standard power socket |
| Mobility | Carry handle + casters |