Portable Resistive Load Bank Offering Versatile Load Testing Solutions For Power Generation And Distribution Systems
One-line Pitch Thirty kilowatts of resistive load across three phases, ten kilowatts per phase and every phase adjustable on its own — eight breaker steps per phase from 100 W to 4 kW, an unbalanced load capability most banks in this class do not have, and a 50 kg cabinet on casters that fits ...
Thirty kilowatts of resistive load across three phases, ten kilowatts per phase and every phase adjustable on its own — eight breaker steps per phase from 100 W to 4 kW, an unbalanced load capability most banks in this class do not have, and a 50 kg cabinet on casters that fits through a workshop door.
Rated AC 380 V three-phase four-wire, 30 kW in total and 10 kW on each phase. Each phase carries its own breaker bank, so the unit behaves like three independent 10 kW single-phase load banks sharing one chassis — the natural fit for three-phase UPS, inverters and AVRs rather than loading only one phase and extrapolating.
Per phase the steps are 100 W, 200 W, 200 W, 500 W, 1 kW, 2 kW, 2 kW and 4 kW, summing to exactly 10 kW. Combined, they reach every multiple of 100 W from 100 W to 10 kW — for example 3.7 kW on a phase is 2 + 1 + 0.5 + 0.2 kW. Fine resolution at the top of the range and at the bottom, without a variable controller.
Because every phase is switched separately, the bank can run 100 % single-phase load (A phase at 10 kW with B and C at zero), or hold a deliberate 30 / 60 / 90 % imbalance across the three phases. That is what makes it useful for neutral-current, phase-loss and imbalance-tolerance testing, which a ganged three-phase bank physically cannot do.
610 × 400 × 780 mm and ≤ 50 kg with a carry handle and casters, so it can be wheeled between benches. Six 15050 fans push air front to rear, the meter shows power, current and voltage, and protection covers over-temperature alarm, over-voltage, fault alarm and emergency stop. Rated for 7×24 continuous operation, IP20 indoor, ±3% sheet resistors, 1-year warranty.
Yes — each phase is switched independently from 0 to 10 kW, so the extreme case is 100 % single-phase load: 10 kW on phase A with phases B and C at zero. Intermediate imbalances (for example 3 / 6 / 10 kW) are also routine. Note that the neutral must be connected when running highly unbalanced, since the return current flows there.
Minimum step is 100 W per phase. The eight steps sum to 10 kW and can produce every multiple of 100 W in that range — 3.7 kW = 2 + 1 + 0.5 + 0.2 kW, 8.6 kW = 4 + 2 + 2 + 0.5 + 0.1 kW. Values that are not multiples of 100 W, such as 3.75 kW, cannot be set exactly.
The load connects to one set of threaded terminals; system power is a separate standard power socket (AC 220 V auxiliary). At rated 30 kW / 380 V the current is about 45.6 A per phase (calculated). As with any resistive bank, actual power follows the square of the applied voltage, so check the site voltage against the 380 V rating before sizing a test.
Six 15050 fans move air front to rear — keep intake and exhaust clear and leave space around the cabinet. Install indoors, dry and well-ventilated, −10 to 50 °C, IP20. Protection covers over-temperature alarm, over-voltage, fault alarm and emergency stop; 7×24 continuous duty with a 1-year warranty.
| Model name | JH-RYF-30KWA380-W8K |
| Brand | JIANHONG |
| Specification | 610*400*780MM(L*W*H) |
| Weight | ≤50KG |
| Rated voltage | AC 380 V, three-phase four-wire |
| Rated power | 30 kW |
| Auxiliary power supply | AC 220 V 50 Hz |
| Power factor | 1 |
| Resistance accuracy | ±3% (sheet resistor) |
| Cooling system | Forced air cooling, front-to-rear airflow, 6 × 15050 fans (220 VAC power supply) |
| Working environment | Operating temperature: -10 to 50 °C; dry and well-ventilated |
| Control Method | Manual air circuit breaker control |
| IP class | IP20 (indoor use) |
| Display mode | Digital display of power, current and voltage |
| Adjustable Steps | Phase A: 100 W, 200 W, 200 W, 500 W, 1 kW, 2 kW, 2 kW, 4 kW Phase B: 100 W, 200 W, 200 W, 500 W, 1 kW, 2 kW, 2 kW, 4 kW Phase C: 100 W, 200 W, 200 W, 500 W, 1 kW, 2 kW, 2 kW, 4 kW |
| Load Note | Unbalanced loading possible (each phase independently adjustable) |
| Load protection | Over-temperature alarm, over-voltage protection, fault alarm, emergency stop |
| Duty Cycle | Continuous online operation, 7×24 duty; 1-year warranty |
| Output | 1 set of load: threaded terminals 1 set of system power: power socket |
| Mobility | Carry handle + casters |