Portable Resistive Load Bank Offering Load Simulation Capabilities For Routine Testing And Maintenance Of Electrical Power Systems
One-line Pitch A 40 kW DC load bank that covers 200–320 V, sets load in 1 kW steps on a touch screen, and reports voltage, current and power at 0.5S class — with RS485 for automatic test systems and a 15-year resistor life behind a 7×24 duty rating. Product Features 1.1 One Cabinet for the 200–320 V ...
A 40 kW DC load bank that covers 200–320 V, sets load in 1 kW steps on a touch screen, and reports voltage, current and power at 0.5S class — with RS485 for automatic test systems and a 15-year resistor life behind a 7×24 duty rating.
Rated for DC 200–320 V, so the same unit covers the 200 V, 240 V, 280 V and 320 V DC buses found in rectifier, telecom and battery-string systems instead of one bank per voltage class. Rated power is 40 kW; the load is purely resistive (power factor 0.99) and the maximum voltage is 1.1 × rated.
Load is set in 1 kW increments across the whole 1–40 kW range — no gaps at the low end, which matters when you need to hold a converter at 8 kW or 13 kW rather than at a round 10 kW or 20 kW step. Fine granularity also lets you step a source through its efficiency curve without changing hardware.
Local operation is on the touch screen; remote control is over RS485, so the bank can be driven from an aging-room controller or a lab test sequence. The display shows voltage, current and power at 0.5S measurement class, and the meter reads down to 0.8 A — enough to see light-load behaviour, which is where many DC sources are least stable.
Continuous online operation on a 7×24 basis, with a 15-year resistor service life and resistors held to ±3%. Protections cover over-voltage, over-temperature alarm, fan-fault alarm and emergency stop. The cabinet is IP20 for indoor use, stands on casters at ≤150 kg, and is 800 × 700 × 1310 mm — small enough to move between benches.
The load is purely resistive, so power follows the square of the applied voltage: at half the voltage you get a quarter of the power. The rated 40 kW is quoted at the rated voltage — for a specific operating point, tell us the bus voltage and we will give you the corresponding kW and current.
Load is set in 1 kW steps from 1 kW up to 40 kW on the touch screen, so any whole-kilowatt point in that range can be dialled in directly — 7 kW, 23 kW, 38 kW, no need to settle for the nearest 5 kW or 10 kW step.
Yes — remote control is over RS485, with local operation on the touch screen. Measurement is 0.5S class for voltage, current and power, and the meter reads from 0.8 A upward. If you tell us the host controller you use, we can confirm the protocol details before you design the rack around it.
Forced air cooling, front intake and rear exhaust, so the rack must leave the front and back clear. For indoor use at IP20, ambient −10 to 50 °C, dry and well-ventilated. Protections are over-voltage, over-temperature alarm, fan-fault alarm and emergency stop. Continuous 7×24 duty, 1-year warranty on the unit, 15-year resistor life.
| Model name | JH-RYF-40KWD200D320-P |
| Brand | JIANHONG |
| Specification | 800 × 700 × 1310 mm (L × W × H) |
| Weight | ≤ 150 kg |
| Rated voltage | DC 200 V – DC 320 V |
| Rated power | 40 kW |
| Auxiliary power supply | AC 220 V / 50 Hz |
| Power factor | 0.99 |
| Resistance accuracy | ±3% (high-precision, compact, ultra-light resistors used in the load bank) |
| Cooling system | Forced air cooling, front intake, rear exhaust |
| Working environment | Operating temperature: -10 to 50 °C; dry, well-ventilated |
| Local Control | Touch screen |
| Remote Control | RS485 |
| IP class | IP20 (indoor use) |
| Display mode | Voltage, current and power displayed (measurement accuracy class 0.5S) |
| Meter Lower Limit | 0.8 A |
| Power Adjustment Range | 1 kW – 40 kW |
| Step Resolution | 1 kW |
| Load Note | 1. Maximum voltage is 1.1 × rated voltage. 2. The rated 40 kW is reached only at the rated voltage; at any other voltage the power follows Ohm's law. |
| Load Protection | Over-voltage protection, over-temperature alarm, emergency stop, fan fault alarm |
| Duty Cycle | Continuous online operation, 7×24 duty; resistor service life 15 years |
| Load Connection | Terminal posts |
| Auxiliary Power Connection | Standard power socket |
| Enclosure Colour | Computer white DH-1928 |
| Mobility | Casters |