Heavy Duty Resistive Load Bank Offering Stable Load Conditions and Supporting Preventive Maintenance of Electrical Equipment
One-line Pitch Sixteen independent 20 A / DC 450 V resistive channels in one 300 kg cabinet: set each channel in 1 A steps, switch it with its own breaker, and leave it running 7×24 — built for testing many small DC sources at once rather than one big one. Product Features 1.1 16 Independent ...
Sixteen independent 20 A / DC 450 V resistive channels in one 300 kg cabinet: set each channel in 1 A steps, switch it with its own breaker, and leave it running 7×24 — built for testing many small DC sources at once rather than one big one.
Each of the 16 channels carries up to 20 A at DC 450 V and is switched by its own air circuit breaker, so one cabinet serves 16 units under test at the same time. Channels can be used together or in any subset, and a fault on one branch does not take the others offline.
Steps are 1 A, 2 A, 2 A, 5 A and 10 A, combinable to any whole-amp value from 1 A to 20 A — 7 A, 13 A, 18 A are all directly settable. For batch testing that means each DUT can be loaded at its own rated current instead of being rounded to the nearest 5 A or 10 A.
Power factor 1, resistance tolerance ±3%, continuous online operation on a 7×24 basis and a 15-year resistor service life — the duty profile of an aging room rather than a lab bench. Noise stays under 75 dB at 1 m, which matters when 16 channels run in the same room as people.
There is no meter, no communication and no protection circuit in this model: the current path is resistors plus breakers, nothing else. That keeps the bill of materials and the failure modes small, and makes maintenance a breaker-and-resistor job. Readings come from your own instruments; system-level over-voltage and over-temperature protection should sit on the DUT side.
Yes. Each channel is rated 20 A at DC 450 V and has its own breaker, so all 16 can be loaded simultaneously or any subset used independently. Tell us your total current requirement and we will confirm the matching model.
1 A. The five steps (1 A, 2 A, 2 A, 5 A, 10 A) combine to any whole-amp value between 1 A and 20 A — for example 13 A = 10 A + 2 A + 1 A.
This model has none of the three — no display, no communication and no load protection circuit. Current and voltage are read on your own instruments, and over-voltage / over-temperature protection should be provided on the DUT or system side. If you need a metered or RS485-controlled version, we build those too — tell us and we will quote the matching configuration.
Forced air cooling, front intake and rear exhaust, so keep the front and back clear. Noise is below 75 dB at 1 m. Cabinet is 600 × 800 × 2100 mm at ≤300 kg on casters, IP20 for indoor use, ambient −10 to 50 °C, dry and well-ventilated.
| Model name | JH-RYF-9KWD450-A5K-16L-BX |
| Brand | JIANHONG |
| Dimensions | 600 × 800 × 2100 mm (L × W × H) |
| Weight | ≤ 300 kg |
| Rated voltage | DC 450 V |
| Rated Current | 20 A × 16 channels |
| Auxiliary power supply | AC 220 V |
| Power factor | 1 |
| Resistance accuracy | ±3% (high-precision, compact, ultra-light resistors used in the load bank) |
| Cooling system | Forced air cooling, front intake, rear exhaust |
| Working environment | Operating temperature: -10 to 50 °C; dry, well-ventilated |
| Local Control | Air circuit breaker (MCB) control |
| Remote Control | None |
| IP class | IP20 (indoor) |
| Display mode | None |
| Current Steps | 1 A, 2 A, 2 A, 5 A, 10 A (can be combined) |
| Step Resolution | 1 A |
| Load Protection | None |
| Duty Cycle | Continuous online operation, 7×24 duty; resistor service life 15 years |
| Noise | Less than 75 dB at 1 m |
| Load Connection | Terminal block |
| Auxiliary Power Connection | Terminal block |
| Enclosure Colour | Computer white DH-1928 |
| Mobility | Casters |