Product Features
1. Multi-step current combination adjustment with support for step stacking; step adjustment accuracy of up to 1 A; flexible load configuration to accommodate a wide range of load testing requirements.
2. Features a built-in forced-air cooling system with unidirectional airflow from right to left, combined with a high-power 150×50 fan, ensuring that temperature rises remain under control during prolonged continuous operation.
3. Integrated multi-layered safety protection, including overheat warning, overvoltage protection and an emergency stop button; the upper voltage limit is set at 1.1 times the rated voltage to mitigate the risk of overload during testing.
4. Dual-channel data is displayed simultaneously, allowing real-time readings of power, current, voltage and apparent power; the test data is presented in an intuitive and easy-to-read format, facilitating on-site recording and verification.
5. The integrated carrying handle and castor design ensures the unit’s weight is manageable, making it easy to move around indoor venues; the terminal block clearly separates the resistance output terminals from the auxiliary power supply connections, ensuring neat and organised wiring.
Application Scenarios
Testing the ageing and discharge performance of finished Uninterruptible Power Supply (UPS) units to verify output stability under full-load and segmented-load conditions.
Charging points and AC power modules undergo load testing prior to leaving the factory to verify their output voltage, current and continuous load-carrying capacity.
Load testing of the small-scale prototype of the generator set, simulating real-world electrical loads, to investigate issues relating to voltage drop and overheating under load.
Reliability ageing tests on electrical products such as power adaptors and regulated power supplies.
Common Questions & Answers
Q1: Can several of these load cabinets be used in parallel?
A: This unit supports the stacking of internal current settings for a single unit, but the model itself does not support direct parallel connection of multiple units to increase capacity; if a higher-power load is required, a corresponding high-power model must be selected.
Q2: Can the equipment be used outdoors in the open air?
A: Protection rating IP20; suitable only for dry, well-ventilated indoor environments; must not be used in outdoor settings where it may be exposed to rain or heavy dust.
Q3: Are the auxiliary power supply and the load output part of the same circuit?
A: No, the auxiliary power supply is a separate 220 V AC circuit that powers the equipment’s control system, display and fan; the resistive load circuit is routed separately from the threaded terminals, so the two circuits are distinct.
Q4: Is additional heat dissipation modification required for prolonged continuous operation at full load?
A: The unit comes as standard with factory-fitted directional forced-air cooling, designed for continuous 24/7 operation; however, ensure that there are no obstructions around the cabinet, allow sufficient space for ventilation, and do not block the air inlets and outlets.
Q5: What happens if the input voltage exceeds the rated value?
A: It features built-in overvoltage protection; when the voltage exceeds 1.1 times the rated voltage, the protection is triggered, stopping the current flow to prevent damage to the resistor and internal components.
| Product parameters | ||
|---|---|---|
| Model | JH-RYF-22KWA220-A8A | |
| Brand | Jianhong | |
| Dimensions | ≤400*550*770MM (depth × width × height) | |
| weight | ≤50KG | |
| rated voltage |
AC220V 50HZ |
|
| rated power |
|
|
| accessory power supply | AC220V 50HZ | |
| power factor | 1 | |
| Resistance accuracy |
±3%(Sheet resistor) |
|
| Cold mode |
Forced air cooling, from right to left, 15050 fan |
|
| Work environment |
Operating temperature: -10 to 50 °C, dry and well-ventilated |
|
| Local control mode | Button controls | |
| Class of protection | IP20 (Indoor) | |
| display mode |
Two-channel digital display of power, current, voltage and apparent power |
|
|
Current ranges |
|
|
|
Stepping accuracy |
1A |
|
| Load protection |
Overheating alarm, overvoltage protection (maximum voltage is 1.1 times the rated voltage), emergency stop |
|
|
working |
Capable of continuous online operation, 24/7 operation, 1-year warranty |
|
|
Load input method |
A set of resistor terminals: threaded terminals A set of auxiliary power supply terminals: standard sockets |
|
|
Mobile mode |
Handle + castors | |
Overall Rating